PRECAUTIONS FOR SAFE USE OF DIESEL GENERATOR SETS
DIESEL GENERATOR SETS MUST BE OPERATED BY PERSONNEL FAMILIAR WITH THE STRUCTURE OF THE UNIT AND PROFICIENT IN SAFETY OPERATING PROCEDURES. NEW OR NEWLY OVERHAULED DIESEL UNITS SHOULD UNDERGO 50 HOURS OF RUNNING IN OPERATION ACCORDING TO REGULATIONS AND NECESSARY MAINTENANCE SHOULD BE CARRIED OUT.BEFORE PUTTING NEW OR LONG-TERM UNUSED GENERATORS INTO NORMAL OPERATION, THEY MUST UNDERGO STRICT INSPECTIONS, MAINLY CHECKING THE INSULATION AND WIRING OF THE WINDINGS. IF THERE ARE ANY DISCREPANCIES, NECESSARY MEASURES SHOULD BE TAKEN.AFTER STARTING THE DIESEL ENGINE, THE SPEED SHOULD BE GRADUALLY INCREASED. AFTER CHECKING AND CONFIRMING THAT EVERYTHING IS IN GOOD CONDITION, IT CAN BE OPERATED AT LOW SPEED TO RATED SPEED WITHOUT LOAD. WHEN RUNNING WITHOUT LOAD, PAY ATTENTION TO CHECKING THE OIL PRESSURE FOR ANY ABNORMAL NOISE, EXCITATION CURRENT, THREE-PHASE VOLTAGE CHANGES, ETC. IF THERE ARE ANY ABNORMAL SITUATIONS, STOP THE MACHINE IMMEDIATELY FOR INSPECTION. AFTER INVESTIGATING THE SITUATION, RESTART. IF EVERYTHING IS NORMAL, IT CAN BE PUT INTO NORMAL OPERATION. THE OPERATOR SHOULD CLOSELY MONITOR THE CHANGES IN THE INSTRUMENTS ON THE CONTROL SCREEN TO ENSURE THEY ARE WITHIN THE PERMITTED RANGE, AND MAKE CORRESPONDING ADJUSTMENTS.DURING OPERATION, OPERATORS SHOULD MAINTAIN A SAFE DISTANCE FROM LIVE EQUIPMENT AND WEAR APPROPRIATE PERSONAL PROTECTIVE EQUIPMENT. THE SWITCHING OPERATION SHOULD PAY ATTENTION TO THE SEQUENCE. IF THERE IS A POWER OUTAGE, THE BRANCH SWITCHES SHOULD BE DISCONNECTED FIRST, THEN THE MAIN SWITCH SHOULD BE DISCONNECTED, AND FINALLY THE FOUR POLE DOUBLE THROW KNIFE SWITCH SHOULD BE SWITCHED. WHEN DELIVERING ELECTRICITY, THE SEQUENCE IS REVERSED. NORMAL SHUTDOWN SHOULD FIRST UNLOAD SOME OF THE LOAD, THEN TURN OFF THE MAIN SWITCH, AND FINALLY TURN OFF THE DIESEL ENGINE. IT IS NOT ALLOWED TO TURN OFF THE MAIN SWITCH WITHOUT PULLING IT OFF, AND THE POWER SHOULD BE CUT OFF AUTOMATICALLY WHEN THE DIESEL ENGINE IS TURNED OFF. PERFORM ROUTINE INSPECTIONS ON THE UNIT AFTER SHUTDOWN AND RECORD THE OPERATION STATUS (WORK DIARY).IN CASE OF ELECTRIC SHOCK, THE POWER SWITCH SHOULD BE QUICKLY CUT OFF, OR INSULATED EQUIPMENT SHOULD BE USED TO QUICKLY DISCONNECT OR DETACH THE POWER SUPPLY. THEN CARRY OUT EMERGENCY TREATMENT AND INVITE A DOCTOR TO THE SCENE FOR RESCUE. IN CASE OF ELECTRICAL EQUIPMENT FLOODING, THE RELEVANT POWER SUPPLY SHOULD BE IMMEDIATELY CUT OFF AND REPORTED TO THE LOCAL POWER SUPPLY STATION, AND THEN FIREFIGHTING SHOULD BE CARRIED OUT. DRY FIRE EXTINGUISHERS, CARBON DIOXIDE FIRE EXTINGUISHERS, ETC. SHOULD BE USED FOR EXTINGUISHING FIRES WITH LIVE EQUIPMENT, AND WATER IS NOT ALLOWED.